Mon–Fri: 7am–3pm  |  Walk-In Service
📍 3428 Stanford Dr NE, Albuquerque NM|Cert. of Approval: MS-14 397477
High-Hazard Protection

Purple-K Dry Chemical
Fire Extinguishers

High-performance suppression for Class B liquid and Class C electrical hazards. FSI provides certified annual inspections, recharges, and hydrostatic testing in Albuquerque.

The Choice for Oil, Gas, and Utility Industries

Purple-K dry chemical extinguishers contain potassium bicarbonate—a chemically formulated dry powder agent recognized by fire safety authorities as the most effective dry agent for fighting pressurized liquid and gas fires. It has a distinctive purple tint and outperforms standard dry chemical units in extinguishing speed. It is widely mandated in high-risk zones, such as:

  • Fuel Storage & Distribution: Gas stations, fuel terminals, and airports.
  • Heavy Transportation: Garages, trucking yards, oil tank trucks, and shipyards.
  • Energy Infrastructure: Electrical substations, generator facilities, and gas pipeline nodes.
  • Chemical Engineering: Factories, laboratories, and solvent processing plants.

FSI New Mexico helps Albuquerque industrial sites stay fully compliant with NFPA 10 and OSHA mandates by inspecting, testing, and tagging high-hazard Purple-K extinguishers. Like standard dry chemical, they leave a powder residue, so they are not recommended for clean electronics rooms.

Compliance Rule: Purple-K units carry Class B and Class C ratings only. They must not be deployed on Class A ordinary wood/paper fires, and should always be paired with general-use ABC dry chemical or water units.

Technician checking high-performance industrial fire equipment

Purple-K Specifications & Compliance Checklist

Understanding testing, inspection, and maintenance intervals under NFPA 10 standards.

Specification NFPA 10 / FSI New Mexico Guidelines
Chemical Agent Potassium Bicarbonate dry chemical powder (Purple-K)
Fires Fought Class B (flammable liquids and gases) and Class C (electrical equipment)
Visual Inspection Every 30 days (verify gauge pressure, handle seal, and mounting location)
Annual Maintenance Physical inspection, weight confirmation, and tagging by a licensed fire service company
Internal Inspection Every 6 years (cylinder is emptied, inspected internally, and refilled)
Hydrostatic Testing Every 12 years (cylinder pressure-tested to verify structural shell integrity)

Secure Your Industrial Fire Protection Today

Ensure your heavy-duty Purple-K cylinders are compliant and inspected. Schedule on-site industrial service or walk-in to our shop.

Schedule ServiceCall Now